CP42 Explained: What Catering Equipment Service Providers Need to Know
What is a CP42?
A CP42 is CORGIdirect's Gas Safety Inspection form for commercial catering appliances, used to record the condition of a kitchen's gas installation and its gas appliances on the day of inspection. It is often called a CP42 certificate, although the form is strictly an inspection record. The name comes from CORGIdirect's CP42 form, which only Gas Safe registered businesses can buy. CORGIdirect says the current version reflects IGEM/UP/19 and IGEM/IG/2 and draws on BS 6173, the British Standard for installing and maintaining gas-fired catering appliances. No regulation requires a document called a CP42. It is a common way of recording that a competent engineer inspected the kitchen and what they found, and digital versions of the form are also in use.
What does a CP42 inspection cover?
A CP42 inspection covers the kitchen's gas environment as a whole and the gas appliances within it. CORGIdirect's form is split into two matching parts:
- Part 1, the catering environment: the gas installation and isolation, electrical items, interlocks, and the exhaust and ventilation systems.
- Part 2, the appliances: the gas appliances themselves, such as cookers, ovens, fryers and urns.
Interlocks and ventilation
An interlock links the kitchen's mechanical ventilation to the gas supply, so the gas to the appliances shuts off if the ventilation fails. HSE guidance states that manual bypasses of these interlocks are not permitted. IGEM/UP/19 is the industry standard for interlock systems in commercial catering, and it also sets requirements for testing air quality in commercial kitchens. Older kitchens without an interlock are not automatically failed. HSE's guidance notes that BS 6173 is not retrospective and expects the risk in an existing kitchen with no interlock to be assessed and controlled.
Who can carry out a CP42 inspection?
On most catering premises, a CP42 inspection must be carried out by a Gas Safe registered engineer who is qualified for commercial catering work. HSE's guidance on gas safety in catering and hospitality says the business must be Gas Safe registered and its engineers must hold valid certificates of competence for the types of gas equipment and work involved. Gas Safe registration on its own does not cover every type of gas work. The back of each engineer's Gas Safe ID card lists the categories they are qualified for, and an engineer who services heating systems may not hold the commercial catering categories. For a service provider, the qualification check becomes a scheduling rule. A CP42 job should only go to an engineer whose commercial catering qualifications are current on the day of the visit. Some workplaces sit outside the scope of the Gas Safety (Installation and Use) Regulations 1998, such as factory canteens. The engineer must still be competent there, and HSE describes Gas Safe registration as the clearest way to show it.
How often is a CP42 needed?
Gas safety law in Great Britain does not set a fixed interval for CP42 inspections in commercial kitchens. HSE guidance describes annual inspection as a reasonable minimum, and many in the industry work to a 12-month cycle. The legal duty comes from regulation 35 of the Gas Safety (Installation and Use) Regulations 1998. It requires employers and the self-employed to keep any gas appliance, installation pipework or flue at a place of work under their control in a safe condition. HSE adds that inspection and servicing frequency can vary with the equipment and how it is used, and should follow the manufacturer's recommendations. Customer contracts can also set a shorter interval than 12 months.
Where a 12-month legal deadline does apply
The fixed 12-month safety check in the regulations applies to landlords of residential accommodation. On hospitality sites, that can cover gas appliances serving hotel rooms or staff accommodation, which are recorded on a landlord gas safety record (the CP12 in CORGIdirect's range) rather than a CP42.
What happens if an installation fails?
If an engineer finds an unsafe situation during a CP42 inspection, they classify it under the Gas Industry Unsafe Situations Procedure as either Immediately Dangerous or At Risk. In both cases, the advice to the customer is not to use the appliance or installation.
- Immediately Dangerous (ID): the engineer asks the responsible person's permission to disconnect the appliance or installation from the gas supply.
- At Risk (AR): the engineer asks permission to turn the appliance or installation off.
The procedure is published by the Institution of Gas Engineers and Managers (IGEM), and the current version dates from July 2025. It also sets out when a dangerous gas fitting has to be reported under RIDDOR. For a service provider, a failed CP42 creates follow-on work that needs tracking until the kitchen is safe to use again. A useful record of each failure includes:
- the classification and the appliance it applies to
- the advice given, who received it and whether they agreed to the appliance being turned off or disconnected
- the remedial job raised and the status of its quote
- the retest result once the work is complete
Managing CP42s across multiple sites
Managing CP42s across multiple sites means knowing which inspection is current at every customer kitchen and what is still outstanding from the last one. Without that view at contract level, overdue inspections and unresolved findings are easy to miss.
Link each record to the right site and appliance
Each CP42 relates to one site on one date, while its findings relate to individual appliances. Filing the record against the site and against each appliance it lists means an engineer can check an oven's previous findings before arriving. Appliances also move. When a fryer is replaced or transferred to another kitchen, its inspection history should follow the appliance, and the new unit should be added to the site's records before the next CP42.
Track next inspection dates by contract
CP42 due dates often differ from site to site across a large estate. Some customers want every site inspected in the same month, while others work from each site's last inspection date. Building CP42s into PPM schedules for multi-site contracts lets you combine the gas safety inspection with routine servicing visits. The visit can then be planned around site access windows and the availability of engineers with the right catering categories.
Close out findings and remedial work
Closing out a CP42 means tracking every At Risk or Immediately Dangerous finding until the remedial work is done and retested. Service managers need to see open findings by customer and site, with their age and quote status. Multi-site customers may ask for that information as one report across their estate, so it helps to record findings in a consistent format from the start. Our guide to planning catering equipment maintenance covers the wider maintenance strategy that CP42 inspections sit within.
How digital records help
Digital records keep each CP42 attached to the site and appliances it covers, so due dates, findings and follow-up jobs can be seen together. In practice, that can mean:
- engineers complete the inspection record on a mobile device and the office sees it straight away
- upcoming inspection dates trigger reminders before a site becomes overdue
- remedial jobs are raised against the same appliance as the finding
Service Geeni's catering equipment service management software links service records, PPM schedules and engineer jobs to individual assets.
FAQs
Is a CP42 a legal requirement?
A CP42 form is not named in any regulation. Employers and the self-employed are legally required to keep gas appliances, pipework and flues at work in a safe condition, and a CP42 is a recognised way of showing that a qualified engineer has inspected them.
How long is a CP42 certificate valid?
A CP42 certificate has no fixed legal expiry date. It records the condition of the installation on the inspection date, and because HSE guidance treats annual inspection as a reasonable minimum, planning the next CP42 within 12 months is the sensible default.
Is a CP42 the same as a CP12?
A CP42 and a CP12 are different records. The CP12 is CORGIdirect's landlord gas safety record for residential accommodation, while the CP42 covers commercial catering appliances and the kitchen environment around them.